Input Watts

Formula to convert Input Watts to Amps: A=W/V
Input Watts ÷ Volts = Amps
TOTAL SYSTEM WATTS*
Ballast Type Catalog Designation Lamp Type # of Lamps Input Watts
Magnetic LE
LE
3LE
F40/T12/ES
F40/T12/ES
F40/T12/ES
1
2
3
46
75
118
Magnetic HPF
LE
F96/T12/ES
F96/T12/ES
1
2
79
133
Magnetic HPF
HPF
HPF
HPF
F96/T12/HO
F96/T12/HO
F96/T12/HO/ES
F96/T12/HO/ES
1
2
1
2
148
261
125
223
Magnetic LE
LE
F96/T12/HO
F96/T12/HO/ES
2
2
245
210
Electronic EB12
EB12
3EB12
F40/T12/ES
F40/T12/ES
F40/T12/ES
1
2
3
39
64
93
Electronic EB12
EB12
F96/T12/ES
F96/T12/ES
1
2
71
108
Electronic EB12
EB12
F96/T12/HO
F96/T12/HO/ES
2
2
208
174
Magnetic OCT
OCT
F32/T8
F32/T8
1
2
41
77
Electronic EB8
EB8
3EB8
4EB8
F32/T8
F32/T8
F32/T8
F32/T8
1
2
3
4
40
71
94
114
Electronic EB8
EB8
EB8
F96/T8
F96/T8
F96/HO/T8
1
2
2
71
112
185
Magnetic TT
TT
F40/TT
F40/TT
1
2
49
85
Electronic

EBTT
EBTT
3EBTT

F40/TT
F40/TT
F40/TT

1
2
3
44
75
102
*The Total System Watts refer to the ballast and lamp watts consumed per luminaire. Input watts are based upon ANSI watts as published by ballast manufacturer's literature which is subject to change without notice. Ballast information shown is generic and serves as an approximation only; actual input watts vary according to specific ballast manufacturer and ballast number. For exact input wattage contact either the ballast manufacturer or Columbia Lighting Technical Support.

 

 